The DM series measuring current transformer (TA) allows to reduce the line current to a secondary value of 5A compatible with the amperometric inputs of digital multimeters, protection relays and energy meters.
These devices are suitable for DIN rail mounting.
DM series measuring current transformers are class 1/0.5, without primary winding and are normally used for high primary current values (starting from 50A).
The number of passages of the primary cable does not change the precision characteristics, but reduces the value of the primary current with the same secondary current.
Features
- Operating frequency: 50-60Hz
- Secondary current: 5A
- Permanent overcurrent: 120% Ipn
- Insulation voltage Ui: 720V
- Rated short-time thermal current Ith: 40...60Ipn for 1 second
- Idyn rated dynamic current: 2.5 Ith for 1 second
- Insulation in air: class E
- Attachments:
- Faston for DM2T and DM3T
- screw for DM0T, DM4T and DM35T
- Pluggable terminal covers (only for DM0T, DM4T and DM35T)
- 35mm DIN rail mounting (IEC/EN 60715) or screw mounting (fasteners supplied as standard)
- Degree of protection: IP30
- Environmental conditions:
- operating temperature: -25...+50°C
- storage temperature: -40...+80°C
- relative humidity without condensation: 90%.
- Compliance: IEC/EN 61869-2, IEC/EN 61869-1.